It is general knowledge that electricity consumers must pay for the total amount of kilowatt-hours supplied by the electric utility company, as measured by the corresponding power meter. However, since no electric conductor is perfect and even the highest quality wiring has resistance, part of that electricity is lost between the power meter and the point of use.
What is Voltage Drop?
One of the basic principles of electrical engineering is Ohm’s law, which states that the voltage drop across a conductor or load is equivalent to the product of current and resistance (V = I x R). The electric current is determined by the load on a circuit, while resistance is determined by the physical properties of the conductor.
The concept of voltage drop is used to describe the difference between the voltage supplied at the source and the voltage measured at the load. The factors that determine voltage drop are summarized in the following table:
VOLTAGE DROP FACTORS DESCRIPTION
A. Conductor material Some materials are better electrical conductors than others. For example, copper is more conductive than aluminum.
B. Conductor diameter A wider conductor has improved conductivity because there is more material to carry electric current
C. Conductor length Longer conductors have a higher resistance because the current must travel a longer distance between the source and the load.
D. Conductor temperature Temperature influences the conductivity of materials. Depending on the material and the actual temperature, conductivity may increase or decrease with further increases in temperature.
E. Current carried by the conductor Current is directly proportional to voltage drop. If the current is doubled while resistance is kept the same, the voltage drop also doubles.
F. Connections in the circuit A connection represents an interruption in the conductor material, and there is a contact resistance associated with it. Deficient connections are associated with an increased voltage drop.
How to Calculate Voltage Drop
It is important to note that the voltage drop formula changes depending on the number of phases in the circuit (single-phase or three-phase). In the following equations, the variables used are:
The formulas are divided by 1,000 because standard impedance values are provided for every 1,000 feet. This way, they are converted to ohms per foot. Chapter 9 of the NEC provides conductor properties, based on a 75°C temperature rating.
To demonstrate the procedure, assume a single-phase 120-V circuit carries a current of 22 A, where the conductor impedance is 1.29 ohms per 1,000 ft, and the circuit length is 50 ft. The voltage drop would be:
Voltage drop = ( 2 x 1.29 ohm / kft x 22A x 50 ft ) / 1,000 = 2.84 V
Percentage voltage drop = 2.84V / 120V = 0.0237 = 2.37%
If there is more than one conductor per phase, the calculation above must be divided by the number of conductors per phase, since resistance is reduced. For example, if there are two conductors per phase in the example above, resistance is reduced by half, and the voltage drop would be 1.42V (1.18%).
Select the material either copper or aluminum, the size of the conductor, the voltage and phase from a list of common voltages, then enter the one way circuit length in feet, and load in amperes. This program finds voltage drop, percent voltage drop, and volts at end of circuit.
How Can Voltage Drop Be Controlled?
Since there is no perfect conductor and all materials have electrical resistance, it is impossible to eliminate voltage drop completely. However, there are many ways to minimize it:
Improving system efficiency
Assuming the load stays the same, increasing the efficiency of electrical equipment reduces power consumption. Since the supply voltage is constant, improved efficiency results in less current and a reduced voltage drop.
Troubleshooting
Some electrical issues cause an unnecessary increase in current or resistance, which leads to a higher voltage drop. Once these issues are solved, the voltage drop returns to normal.
Correcting conductor sizes
If the conductors in a circuit are not selected properly, they can experience a significant voltage drop. When selecting conductors, it is important to account for factors such as full-load current, ambient temperature, and the number of conductors in a raceway.
Centralized electrical distribution
If the main electrical shaft and distribution boards are located close to the center of a building, wiring must cross smaller distances to reach the different loads. This type of layout minimizes voltage drop. On the other hand, when the electrical shaft and panels are located at one end of the building, circuits must cross the entire construction to reach loads on the opposite side.
Balanced load distribution
Large commercial buildings typically use three-phase circuits, which have three live conductors as implied by their name. If one phase is too highly loaded, it will also experience a larger current and increased voltage drop compared with the other phases.
These are specific measures that can be deployed to reduce voltage drop. In general, any measure that accomplishes either of the following effects is viable, as long as it is allowed by the NYC Electrical Code:
Decreasing load current
Increasing conductor diameter
Increasing the number of parallel conductors
Decreasing conductor length
Decreasing conductor temperature
Allowable Voltage Drop According to the NEC, 2011 Edition
The NFPA National Electric Code (NEC), which is the basis for the NYC Electrical Code, establishes two conditions for the allowable voltage drop in electrical installations:
The maximum allowable voltage across a branch circuit is 3 percent, measured between the corresponding electrical panel and the farthest outlet delivering power, heating, lighting, or any combination of such loads.
The maximum combined voltage drop across main feeders and branch circuits is 5 percent, measured from the service connection to the farthest power outlet.
These voltage drop levels are considered to provide reasonable operational efficiency. It is important to note that, when circuit conductors are increased in size to compensate for voltage drop, the equipment grounding conductor must be increased accordingly.